- What Does Roof Ventilation Do in an Ontario Winter?
- How Many Roof Vents Do I Need? The 1/300 Rule, Worked Through
- Will a Ridge Vent Fit? Gable Roofs Versus Hip Roofs
- Ridge Vent, Box Vents or Whirlybirds: Which Roof Vents Are Best?
- Why One Attic Gets One Kind of Exhaust Vent
- Air In: Roof Vents Only Work If the Soffit Breathes
- Frost on the Nails: Attic Condensation in January
- When Should Roof Ventilation Be Fixed? During the Re-roof
- Frequently asked questions
- Reader reviews
Key takeaways
- Roof ventilation carries off the water vapour that leaks up from the house before it condenses on the cold roof deck. NRCan calls it the second line of defence, after air sealing.
- NBC 2020, which Ontario's 2024 Code adopts, asks for vent area of at least 1/300 of the insulated ceiling area (1/150 on low slopes), with at least a quarter high and a quarter low. Vent makers split it half and half.
- A 1,200 sq ft attic needs 576 square inches of vent: 288 at the top, which is about 16 feet of ridge vent or six 50 square inch roof vents.
- On a hip roof with all four slopes at one pitch, the ridge is only the house's length minus its width, so a compact two-storey can have too little ridge for a ridge vent to do the job.
- Use one kind of exhaust per attic. Air Vent says never mix them, NRCan says whirlybirds are no more effective than capped vents, and it advises against electric attic fans.
Push the attic hatch open on a frigid January morning and shine a light at the underside of the roof. If every nail tip poking through the deck wears a white cap of frost, your roof ventilation is losing a race it was never meant to run alone. Roof ventilation is the slow draft that enters at the soffits, runs up the underside of the roof deck and leaves near the ridge, and in an Ontario winter its job is to carry off the moisture that leaks up from the house before it settles on cold wood.
Most ventilation advice stops at a picture of a box vent. This guide does the arithmetic: what the Building Code asks for, how many roof vents a real attic needs, when a ridge vent fits and when it cannot, and which vents to leave on the shelf. At Sherak, we install asphalt shingle roofs across York Region, Simcoe, Kawartha and the GTA, and on a re-roof the vents are part of the same job.
Ventilation is also the second half of the fix, not the first. Our guide to preventing ice damming in Ontario explains why a row of new vents rarely cures an ice dam. This one is about getting the vents themselves right.
What Does Roof Ventilation Do in an Ontario Winter?
Roof ventilation moves outdoor air through the attic, in at the soffits and out near the ridge, so the water vapour that leaks up from the house leaves before it condenses on the cold roof deck. In summer the same airflow carries off heat. It cannot stop the air leaks themselves, and it does not cure ice dams.
The National Building Code of Canada 2020, which Ontario's 2024 Building Code adopts, explains in a note to Article 9.19.1.1 why attics are still vented. Controlling the moisture that air leakage and vapour diffusion carry into an attic is necessary to limit deterioration, the note says, and given that imperfections normally exist in vapour barriers and air barrier systems, venting of attic or roof spaces is generally still required. The ceiling below is never perfectly sealed, so the attic needs a way to dry out.
Natural Resources Canada's Keeping the Heat In sets the order. After air sealing, it calls attic ventilation "your second line of defence against the water vapour", and it is plain about the limits: vents "will not prevent condensation and will not solve the problems created by air leakage." A perfectly vented attic still frosts up if a bathroom fan is blowing into it.
How Many Roof Vents Do I Need? The 1/300 Rule, Worked Through
Divide the insulated ceiling area by 300 for the total vent area the Code asks for, then put half of it near the ridge and half at the soffits. A 1,200 sq ft attic needs 4 square feet, or 576 square inches, of vent: 288 at the top, which is six 50 square inch roof vents.
Article 9.19.1.2 sets the number. The unobstructed vent area must be at least 1/300 of the insulated ceiling area, and at least 1/150 where the roof slope is less than 1 in 6 or the roof is built with roof joists. The vents can be roof, eave or gable-end types in any combination, spread uniformly on opposite sides of the building, with at least 25 percent of the required openings at the top of the space and at least 25 percent at the bottom. Ontario adopts this national text through its own regulation, so on new work your municipal building department has the final word.
- Measure the ceiling, not the roof. The figure is the insulated ceiling under the attic, which on a simple house is its footprint. Overhangs and the slope of the roof do not count.
- Divide by 300, or by 150 for a roof flatter than 2 in 12 or one built on roof joists, then multiply by 144 for square inches.
- Split it. The Code's floor is a quarter high and a quarter low. Vent makers and NRCan aim for half and half, and the ventilation calculator in Canplas's technical manual says a home requires an equal amount of intake and exhaust.
- Divide the top half by the vent's net free area, the open area its maker publishes, never the size of the box.
Worked through for common attic sizes, at 1/300 with an even split. The ridge vent columns are in square inches per lineal foot of vent:
| Attic, sq ft | Vent, sq in | At top, sq in | Ridge vent at 18.3, ft | Ridge vent at 12.75, ft | 50 sq in vents |
|---|---|---|---|---|---|
| 1,000 | 480 | 240 | 13.1 | 18.8 | 5 |
| 1,200 | 576 | 288 | 15.7 | 22.6 | 6 |
| 1,500 | 720 | 360 | 19.7 | 28.2 | 8 |
| 2,000 | 960 | 480 | 26.2 | 37.6 | 10 |
| 2,500 | 1,200 | 600 | 32.8 | 47.1 | 12 |
The two ridge vent columns are the two ends of one Ontario maker's range. Canplas, the Barrie company behind Duraflo vents, rates its moulded WeatherPRO ridge vent at 18.3 square inches per lineal foot, and its catalogue lists roll vents down to 12.75. Same attic, over 40 percent more ridge, which is why the vent belongs on a quote by product name. The last column is not an estimate either: for the four attic sizes in its own calculator, Canplas's count of 50 square inch roof vents matches ours.
Will a Ridge Vent Fit? Gable Roofs Versus Hip Roofs
On a gable roof, almost always, because the ridge runs the full length of the house. On a hip roof with all four slopes at one pitch, the ridge is only the house's length minus its width, and the slot has to stop short of both ends, so a compact two-storey can have too little ridge to vent its attic.
The chart works that through for three example footprints, drawn to one scale. Each attic gets its 1/300 vent area split evenly, the ridge vent is rated at Canplas's 18.3 square inches a foot, and the slot stays closed for 12 inches at each end of the ridge, as Canplas's installation guide asks. As a gable, the 36 by 32 foot two-storey has 34 feet of ridge to cut. As a hip, it has 2.
Look at the bungalow too. Its hip ridge takes the vent it needs with about 4 and a half inches to spare, which is no margin at all: switch to a 12.75 square inch roll vent and the same attic needs 25.3 feet of slot against the 18 the roof can give. On a roof like that, the honest answer is a row of static roof vents set just below the ridge, sized to carry the whole top half on their own.

| House | Ceiling area | Vent area needed | At the top | Ridge vent needed | Gable ridge that can be slotted | Hip ridge that can be slotted | Roof vents instead |
|---|---|---|---|---|---|---|---|
| Two-storey, 36 x 32 ft | 1,152 sq ft | 553 sq in | 276 sq in | 15.1 ft | 34 ft, fits | 2 ft, too short | 6 |
| Bungalow, 48 x 28 ft | 1,344 sq ft | 645 sq in | 323 sq in | 17.6 ft | 46 ft, fits | 18 ft, fits | 7 |
| Long bungalow, 60 x 30 ft | 1,800 sq ft | 864 sq in | 432 sq in | 23.6 ft | 58 ft, fits | 28 ft, fits | 9 |
Not sure what your roof can take?
We will quote the roof and its ventilation together, free and with no obligation.
Ridge Vent, Box Vents or Whirlybirds: Which Roof Vents Are Best?
Where the ridge is long enough, a baffled ridge vent, because it exhausts along the whole peak, the highest line in the attic. Where it is not, static roof vents set just below the ridge. NRCan says whirlybirds are no more effective than capped vents, and it advises against electric attic fans.
| Exhaust vent | How it works | Published opening | Best on | Watch for |
|---|---|---|---|---|
| Ridge vent | A 2 inch slot along the peak, covered by the vent and cap shingles | 12.75 to 18.3 sq in a foot (Canplas range) | Gable roofs, long hip ridges | A short ridge; NRCan wants it baffled against wind, water and snow |
| Static roof vent (box vent) | A louvred cap over a square cut-out near the peak | 48 to 130 sq in each (Canplas static vents) | Hip roofs, short ridges | More holes, each one flashed into the shingles |
| Wind turbine (whirlybird) | A head that spins in the wind | Sized by the maker's own chart | Rarely the best pick | NRCan: no suction, no better than a capped vent |
| Gable louvre | A louvred opening in an end wall | Varies by size | Gables where the roof stays uncut | Counts as exhaust, so it does not pair with a ridge vent |
| Power attic fan | An electric fan in the roof or a gable | Rated in airflow, not open area | Not recommended | NRCan: pulls house air into the attic |
Are whirlybirds better than roof vents? NRCan answers it in one line: "Wind-driven, revolving roof vents do not create suction and are no more effective than other types of capped vents." A turbine is also the one moving part on the roof, and Canplas sells a replacement top for turbines that have started squeaking. Lomanco, which makes the Whirlybird, sizes them by its own chart, two 12 inch turbines for an attic of 1,000 to 1,500 square feet, rather than by open area.
Electric attic fans get a firmer no. NRCan advises against them because they can draw more air than the intake supplies: "This will actually pull house air into the attic, resulting in greater heat loss and moisture accumulation. They are also prone to failure, noise production and increased energy use."
The downsides of a ridge vent are the price of its advantages. It needs intake below it, it needs enough ridge, and it has to be built to shed weather. Canplas's instructions call for a slot 2 inches wide, an inch either side of the peak, and it builds baffles into its vent to turn back wind-driven rain and snow. Ask which ridge vent is on your quote, and how it is baffled.
Why One Attic Gets One Kind of Exhaust Vent
Because two kinds of exhaust on one attic can work against each other. One of them can start acting as an intake, so the air takes a shortcut between the two, parts of the attic are bypassed, and rain or snow can be drawn in through the vent that has turned into an intake.
That is Air Vent's position, and it does not hedge: it is never OK to mix two different types of attic exhaust vents over a common attic. Air Vent groups exhaust into five kinds, ridge vents, wind turbines, roof louvres, gable louvres and power vents, and says each uses the wind differently. The Code itself allows roof, eave and gable vents in any combination. The no-mixing rule is the vent makers' advice on making that combination work.
Two cases are worth naming. The first is a gable-ended house with louvres in both end walls that gets a ridge vent on a re-roof: the louvres are exhaust too. The second is the hip roof from the chart, where it is tempting to run whatever ridge vent fits and top it up with box vents. Pick one. If a re-roof moves an attic to a ridge vent, the old roof vents should come off and their holes be decked over and shingled, not left in place as a second exhaust.

Air In: Roof Vents Only Work If the Soffit Breathes
An exhaust vent can only let out what the intake lets in. A ridge vent over a solid, painted or insulation-packed soffit has little air to move, which is why the Code puts at least a quarter of the vent area at the bottom of the attic and the vent makers put half there.
Article 9.19.1.3 protects the path between the two. It wants at least 63 mm between the top of the insulation and the underside of the roof sheathing. At the eaves, where baffles hold the insulation back, it wants an air space of at least 25 mm that is large enough for the required venting, and the baffles must extend at least 50 mm above the top of the insulation. Ceiling insulation must not restrict the flow of air through roof vents or any part of the attic.
How much vented soffit a roofline needs is worked out in our soffit and fascia guide, and on a house with no overhang to vent, its section on vented fascia covers what takes over at the edge. On District Avenue in Vaughan in May 2025, we replaced the soffit around the whole house with a vented aluminum system to improve the attic's ventilation, with aluminum-clad fascia and new seamless eavestrough on the same job. When the intake is the problem, that is a soffit and fascia job, not a roof job.
Frost on the Nails: Attic Condensation in January
Frost on the nail tips and the underside of the deck after a cold snap means moist house air is reaching the attic. NRCan expects some frost. Heavy buildup, 10 mm or more, is the cue to check that the vents are there and not blocked with insulation, and because the vapour comes up from the house, to look for the leaks too.
Look during or just after a cold snap, which is when NRCan says condensation shows up as frost in a cold climate, and look hardest above the bathrooms, around the attic hatch, and wherever a pipe, duct or wire comes up through the ceiling. NRCan's line on the source is short: moisture can come from inside the house, carried into the attic as water vapour by air leakage.
A bathroom fan that ends in the attic, or whose duct has come apart, delivers shower steam straight to the cold deck. The Code does not allow a fan to exhaust into an attic, and our article on a bathroom fan dripping water works out how much water one shower sends up the duct. That frost has a second act. On the first mild day it melts, and the water can reach the ceiling below, which looks like a roof leak with no rain in the forecast.
More roof vents are the tempting fix, and the wrong first one. Seal the leaks, then make sure the vents you already have are clear and balanced, which is the same order that stops ice dams.

When Should Roof Ventilation Be Fixed? During the Re-roof
During a roof replacement, if you can. With the shingles off, a ridge slot can be cut, old vents pulled and their holes decked over, and the deck checked while it is open. The warranties on the shingles we install also exclude damage caused by inadequate ventilation, so the new roof depends on getting it right.
When we re-roofed a house on Brant Street East in Orillia on March 27 and 28, 2025, the wood decking under the old shingles had deteriorated. We replaced all of it, and installed new, upgraded ventilation in the same two days. That is what a re-roof makes possible: the deck is open, the crew is already on the roof, and the vents go on with the new shingles.
The warranty side is set out in our guide to the best asphalt shingles for Ontario: the warranty excludes damage caused by inadequate ventilation and expects the venting to meet code for total area, distributed between the ridge and the eaves. On our roof replacement cost breakdown, ventilation is one of the lines that separates a low quote, with the old vents reused, from one with intake and exhaust balanced to the code ratio. Ask every quote to name the exhaust and the intake, with the area worked out.
We back the work with a 10 year workmanship warranty, carry $5 million in liability insurance, and take 10 percent of the price only once you are satisfied. If you are planning a re-roof, or you have found frost in the attic, get a free quote and tell us what you are seeing. We are based in Gormley and work across York Region, Simcoe, Kawartha and the GTA, from Whitchurch-Stouffville to Orillia.
Sherak Ltd, Head Office
12275 Woodbine Avenue, Gormley, ON L0H 1G0
Phone: +1 905 490 8800
Email: info@sherak.ca
Re-roofing, or chasing attic frost?
We will quote the roof and its ventilation together, free and with no obligation. 10 year workmanship warranty and $5 million liability insurance.
Get a Free QuoteFrequently asked questions
How many roof vents do I need for a 1,200 sq ft house?
Are whirlybirds better than roof vents?
Should a ridge vent go all the way to the end of the roof?
Is it okay to have gable vents with a ridge vent?
Can rain or snow get in through roof vents?
Do you put shingles over a ridge vent?
Does my attic need roof vents if it has soffit vents?