Siding & Exteriors

Soffit and Fascia in Ontario: A 2026 Guide to Vents, Rot and Cost

Emad AlikhanpourRoofing & Exterior Specialist•March 18, 2020• 36 min read•Updated November 16, 2026
Soffit and Fascia in Ontario: A 2026 Guide to Vents, Rot and Cost
Prefer to listen?PodcastWhy Your Roof Needs to Breathe · 23 min listen
On this page

Key takeaways

  • Soffit and fascia get quoted as one job and fail as two. Soffit fails when air stops moving through it. Fascia fails when water gets in behind it. Almost nothing that damages one has anything to do with the other.
  • Vented soffit panels carry a published ventilation figure per lineal foot, and in Gentek's product directory those figures run from 2.3 square inches up to 10. Two panels that look identical from your driveway can differ by more than four to one.
  • The National Building Code, which Ontario's 2024 Building Code adopts, asks for one square foot of unobstructed vent per 300 square feet of insulated ceiling, at least a quarter of it low and a quarter high. Behind a baffle at the eave it accepts as little as 25 mm of clear air, and blown insulation closes that inch easily.
  • A house with little or no overhang can still breathe at the eave. Vented fascia, vented drip edge and edge vents publish 6.3 to 10 square inches a foot, against 4.02 for the common 16 inch vented aluminum soffit.
  • Rotten fascia is almost never a fascia problem. It is an eavestrough overflowing at the back, a missing drip edge, shingles stopping short, or ice standing on the eave. Capping over it in aluminum hides the cause and fixes nothing.
  • Most Sherak soffit and fascia installations run $1,500 to $4,000. Of the 42 soffit and fascia jobs in our published portfolio, not one was done on its own: 37 included eavestrough work and 26 included siding.

Stand under the edge of your roof and look straight up. The flat panel over your head is the soffit. The board facing you at the roof edge, the one your eavestrough is screwed into, is the fascia. Soffit and fascia are quoted together, ordered together and fitted together, which is why almost every Ontario homeowner files them as one thing.

They are not one thing. They fail for completely unrelated reasons. Soffit is an air problem you cannot see from the ground. Fascia is a water problem you can see and almost always misread. Get those two backwards and you pay twice: a beautiful new roofline on the outside, and the same wet board underneath it.

So this article runs in two halves, because the parts do. The first half is about air, and it turns on a number soffit makers publish for their vented panels, which almost nobody reads. The second half is about water, and it turns on the fact that rotten fascia is hardly ever caused by the fascia.

Every figure below comes from the National Building Code that Ontario's Building Code adopts, a manufacturer's own published spec sheet, a federal guide, or Sherak's own project record. Where a price is ours, we say so.

Soffit and Fascia Do Two Different Jobs

The soffit is the horizontal underside of your roof overhang and its job is to let outside air into the attic. The fascia is the vertical board at the ends of the rafters and its job is to close the roof edge and carry the eavestrough. One is a ventilation part. The other is a structural and water part.

They meet at the same corner of the house and have almost nothing to do with each other. That is the single most useful thing to understand before anyone quotes you.

On a typical Ontario house the soffit is a perforated aluminum or vinyl panel, cut to the depth of the overhang and laid side by side along it, held in a channel at the wall and another at the fascia. The fascia behind the eavestrough is a softwood board, often a 1x6 or a 1x8, nailed across the rafter tails. On most houses that board is wrapped in a bent aluminum cover so you never see the wood again.

That aluminum cover is the source of most of the confusion in this trade. It is a jacket, not a board. It carries nothing, it holds no screws, and the eavestrough hangers driven through it are anchored in the wood behind. When somebody says their fascia is aluminum, what they usually mean is that their wood fascia is wearing aluminum.

SoffitFascia
Where it isThe flat underside of the roof overhangThe vertical board across the rafter ends
What it doesLets outside air into the atticCloses the roof edge and carries the eavestrough
What kills itBlocked intake, then trapped moistureWater reaching the wood and staying there
How you noticeIce dams, a baking attic, mould on the sheathing, animals in the overhangSagging trough, brown streaks, soft wood, paint lifting
What it damages nextThe roof deck and the shingles above itThe trough, the wall below it, the foundation
Usual material hereVented aluminum or vinyl panelSpruce or pine board, usually capped in aluminum

In our own record they almost always travel together: 40 of the 42 soffit and fascia jobs in our portfolio included both, because the crew is already on the ladder and the eavestrough has to come off either way. That is a scheduling argument, not an engineering one. Diagnose them separately.

Here is where each part sits, and what each one is there to do.

Old cream painted wooden soffit on an Ontario house with a single small round vent and a water stained fascia board above it
Illustration: one small round vent in a painted plywood soffit, with a stained fascia above it. Both halves of the problem in one picture.
Where the soffit and fascia sit at the edge of a roof, and what each part does (Sherak section drawing, to scale)
12345671ShinglesShed water down the roof and over the edge into thetrough.2Drip edgeMetal along the eave that carries water off the roofedge and into the trough, clear of the fascia.3EavestroughCatches the roof water and takes it to thedownspouts. Its hangers screw into the fascia board.4FasciaThe board across the rafter ends. It closes the roofedge and carries the trough. Usually wood, wrappedin aluminum.5SoffitThe perforated panel under the overhang. Outside aircomes into the attic through it.6BaffleHolds the insulation off the roof deck so the airfrom the soffit can get past the wall.7InsulationKeeps the house heat out of the attic. It must notbury the air path at the eave.Drawn to scale: a 6 in 12 pitch, a 16 in overhang, a 1x8fascia board (7.25 in face) and a 5 in eavestrough.Real houses vary. The parts and the order they meet in do not.
Where the soffit and fascia sit at the edge of a roof, and what each part does (Sherak section drawing, to scale)
NumberPartWhat it does
1ShinglesShed water down the roof and over the edge into the trough.
2Drip edgeMetal along the eave that carries water off the roof edge and into the trough, clear of the fascia.
3EavestroughCatches the roof water and takes it to the downspouts. Its hangers screw into the fascia board.
4FasciaThe board across the rafter ends. It closes the roof edge and carries the trough. Usually wood, wrapped in aluminum.
5SoffitThe perforated panel under the overhang. Outside air comes into the attic through it.
6BaffleHolds the insulation off the roof deck so the air from the soffit can get past the wall.
7InsulationKeeps the house heat out of the attic. It must not bury the air path at the eave.
Soffit and Fascia in Ontario: When "Vented" Moves No Air

What Does Soffit Actually Do?

Soffit is the air intake for your roof. Warm damp air leaves the attic at the ridge, and cool outside air has to come in somewhere low to replace it. On nearly every Ontario house that somewhere is the perforated panel under the overhang. Block it and the attic stops breathing, whatever is fitted at the top.

An attic is not insulated to be warm. It is deliberately kept as close to the outdoor temperature as possible, and ventilation is how that happens. Air enters low at the soffit, runs up the underside of the roof deck, picks up heat and water vapour that leaked out of the house below, and leaves at the ridge or through roof vents near the peak.

One thing goes wrong straight away when that stops. In winter, moisture that should have left the attic condenses on the cold underside of the sheathing instead. You get frost on the nail points, then black staining across the plywood, then in a bad year a drip through the ceiling in March that looks exactly like a roof leak and is not one.

There is a second failure and it is the expensive one. A warm attic melts snow on the roof deck above it, the meltwater runs down to the cold overhang and freezes there, and you have an ice dam. Our guide to preventing ice damming in Ontario works through that in full, including why CMHC's fact sheet on attic venting and ice dams calls adding ventilation to a wet attic "the wrong approach": its fix for ice dams is to seal the attic air leaks and insulate thoroughly. The intake at the soffit is a separate question. Where vents are required, the Code requires some of them low, and an exhaust vent at the ridge with no intake below it has little to draw on.

Ontario's 2024 Building Code adopts the National Building Code text here, and Article 9.19.1.1 of NBC 2020 puts it plainly: unless it can be shown to be unnecessary, where insulation sits between a ceiling and the roof sheathing, a space has to be left between the two, and vents have to be installed to carry moisture from that space to the outside. Not recommended. Required.

Article 9.19.1.2 then says how those vents have to be spread out. They can be roof, eave or gable end vents in any mix, but they sit uniformly on opposite sides of the building, with not less than 25 percent of the required openings at the top of the space and not less than 25 percent at the bottom. On most houses the bottom is your soffit. The Code will not let you buy your way out of intake by adding ridge vent. Ontario adopts this national text through its own amendment document, so on new work your municipal building department has the final word.

How Much Vented Soffit Does an Ontario House Need?

The Building Code asks for one square foot of unobstructed vent for every 300 square feet of insulated ceiling. On a 1,500 square foot bungalow that is 720 square inches of vent in total. Split evenly between the eave and the peak, 360 square inches of it has to be working intake at the soffit.

Run the arithmetic once and you will never have to trust a salesperson's opinion on it again.

Take the insulated ceiling area, not the floor area of the house. That distinction matters enormously on a two storey, where the attic only sits over the upper floor. A 2,400 square foot two storey with a 1,200 square foot footprint has 1,200 square feet of insulated ceiling, not 2,400.

Divide that by 300. That gives you the required vent area in square feet. Multiply by 144 to get square inches, because every soffit panel on the market publishes its figure in square inches.

Insulated ceilingTotal vent required (1 in 300)Balanced intake at the soffitCode minimum at the bottom (25 percent)
1,000 sq ft480 sq in240 sq in120 sq in
1,500 sq ft720 sq in360 sq in180 sq in
2,000 sq ft960 sq in480 sq in240 sq in
2,500 sq ft1,200 sq in600 sq in300 sq in

Two footnotes on that table, both of which come up on real quotes.

The code minimum in the last column is a floor, not a target. Twenty five percent at the bottom is what the Code will accept, and vent makers size to an even split: Lomanco's sizing table pairs a 1,500 square foot attic's 360 square inches of exhaust with 60 feet of its edge vent, which at 6.3 square inches a foot is 378 of intake: an even split. The reason is worth knowing. When exhaust at the ridge outweighs intake at the eave, the ridge starts pulling replacement air down through the nearest other opening, which is often another roof vent a few feet away. The air short circuits across the peak and the far end of the attic barely moves. Air Vent, for its part, does not recommend mixing two types of exhaust vent on one roof.

The ratio also changes on a low roof. Where the slope is less than 1 in 6, or where the roof is framed with joists rather than trusses and there is no attic to speak of, the code doubles the requirement to 1 in 150. Anyone quoting a low sloped rear addition should know that without being asked.

One last piece of good news, because there is not much of it in this section. A hip roof gives you eave on all four sides. A gable roof gives you eave on two. On the 30 by 50 foot bungalow in the next drawing, that is 160 feet of eave as a hip against 100 as a gable, which is why the same panel that struggles on one house is comfortable on the other.

Vented Is Not a Specification

Vented soffit panels carry a published ventilation figure per lineal foot, and the figures are nothing alike. Gentek's own product directory lists its vented panels from 2.3 square inches a foot up to 10. All of them are sold as vented. All of them look much the same from the driveway. One needs four times the roofline of the other.

This is the number nobody reads, so here it is, straight out of a manufacturer's published catalogue rather than out of anyone's opinion.

Soffit panelPublished ventilation per lineal foot
Vinyl, 12 in T-4, hidden vent10 sq in
Vinyl, 12 in T-4, fully vented7.1 sq in
Aluminum, 18 in 3-panel, vented5.46 sq in
Vinyl, 10 in D-5, fully vented5.3 sq in
Aluminum, 16 in 4-panel, vented4.12 sq in
Aluminum, 16 in 2-panel, vented4.02 sq in
Vinyl, 8 in beaded, vented2.4 sq in
Vinyl, 12 in T-4, centre vented2.3 sq in

Every one of those is a real product in the Gentek product directory, which calls the figure the panel's net free open area. It is driven by how much of the panel face is actually perforated. A centre vented panel is perforated only down its middle. A fully vented panel is perforated across its face. Both are sold under the word vented.

Now turn each of those figures into the thing a homeowner can check: how much of your roofline has to be that panel before the attic can breathe.

Feet of vented soffit needed to make the intake for a 1,500 sq ft attic (Sources: Gentek Product Directory published ventilation figures; NBC 2020 Article 9.19.1.2, adopted in Ontario)
roofline this panel needsroofline the house does not have100 ft of eaveVinyl 12 in T-4, hidden vent10 sq in/ft64 ft to spare36 ftVinyl 12 in T-4, fully vented7.1 sq in/ft49 ft to spare51 ftAluminum 18 in 3-panel, vented5.46 sq in/ft34 ft to spare66 ftAluminum 16 in 4-panel, vented4.12 sq in/ft13 ft to spare87 ftAluminum 16 in 2-panel, vented4.02 sq in/ft10 ft to spare90 ftVinyl 12 in T-4, centre vented2.3 sq in/ft57 ft short157 ft04080120160 ftEach run is 360 sq in of intake divided by the panel's own figure.Every panel here is sold as vented. Only the length of eave it takes changes.
Feet of vented soffit needed to make the intake for a 1,500 sq ft attic (Sources: Gentek Product Directory published ventilation figures; NBC 2020 Article 9.19.1.2, adopted in Ontario)
Soffit panelPublished ventilation per lineal footFeet of it needed for 360 square inches of intakeAgainst 100 feet of eave
Vinyl 12 in T-4, hidden vent10 sq in36 ft64 ft to spare
Vinyl 12 in T-4, fully vented7.1 sq in51 ft49 ft to spare
Aluminum 18 in 3-panel, vented5.46 sq in66 ft34 ft to spare
Aluminum 16 in 4-panel, vented4.12 sq in87 ft13 ft to spare
Aluminum 16 in 2-panel, vented4.02 sq in90 ft10 ft to spare
Vinyl 12 in T-4, centre vented2.3 sq in157 ft57 ft short

Read That Drawing Again, Because It Is Not Comfortable

The dashed line is a 30 by 50 foot bungalow with a gable roof. Eave down both 50 foot sides, so 100 feet of roofline to work with, which sounds like plenty until you put a panel against it.

The 16 inch vented aluminum panel needs 90 of those 100 feet to be continuously vented. That is not a margin. That is the whole roofline minus the returns at each corner, and it assumes every single panel up there is the vented one and every perforation in it is open.

The centre vented vinyl panel cannot do it at all. It needs 157 feet of eave and the house has 100. No installer, however careful, can make that house breathe with that product, and nothing about the finished job would look wrong.

A two storey comes out looser, as it happens. A 25 by 40 footprint carrying 1,000 square feet of insulated ceiling needs 240 square inches of intake and offers 80 feet of gable eave. At 4.02 square inches a foot that is 60 of the 80 feet: three quarters of the eave, against nine tenths on the bungalow. The eave shrinks more slowly than the ceiling, so a smaller attic is easier to feed. The centre vented panel still needs 104 feet, and still cannot do it.

This is why the panel's name and code belong on a quote rather than the word vented, and why the run should be counted before anything is ordered. It is also how a roofline replaced a few years ago can still sit over an attic that does not move air. Nothing was done wrong in any way anyone would notice. The wrong box was opened.

Close view from below of a white vented aluminum soffit panel showing the narrow perforated strip running down the centre of the panel
Illustration: a centre vented panel seen from below. One perforated strip down the middle, and no way to read its figure without the product code.

The 25 Millimetres That Decide Everything

Vent area on paper counts for nothing if the air cannot get past the insulation. At the junction of the roof and the wall, where a baffle holds the space open, the Building Code will accept a clear air path of 25 mm. That single inch is the doorway for the entire attic, and a hose blowing cellulose closes it in moments.

Article 9.19.1.3 of NBC 2020 is three sentences long and it is the most consequential thing in this article.

Sentence one: not less than 63 mm of space between the top of the insulation and the underside of the roof sheathing. Sentence two: at the junction of sloped roofs and exterior walls, where preformed baffles hold the insulation back, the baffle has to keep an air space of not less than 25 mm, large enough to meet the venting requirement, and extend not less than 50 mm above the top of the insulation. Sentence three, and this is the one nobody quotes: ceiling insulation shall be installed so that it will not restrict the free flow of air through roof vents or through any part of the attic.

Natural Resources Canada's retrofit guide, Keeping the Heat In, asks for more room at the eave than the 25 mm floor. It says to leave 38 to 50 mm between the top of the insulation and the underside of the sheathing, and to use baffles between each rafter space so it stays that way. It also says, in the same breath, that batts should cover the top plate of the exterior wall but not block the venting.

Read those two instructions together and you have the whole conflict of the modern Ontario attic. The insulation must reach out over the wall plate, because the corner above the wall is the coldest part of the ceiling and the place ice dams start. The air must also get past that exact point, because it is the only way in. Two requirements, one wedge of space, often only a few inches tall where the rafter crosses the wall.

The clear air path required over the insulation at the eave (Sources: NBC 2020 Article 9.19.1.3, adopted in Ontario; Natural Resources Canada, Keeping the Heat In)
roof sheathingthe air pathinsulationInsulation blown tight to the deckno baffle, loose fill packed inno path0 mmBaffle at the wall junctionNBC 9.19.1.3(2), the minimum25 mmWhat NRCan recommends38 to 50 mm50 mmEverywhere else above the insulationNBC 9.19.1.3(1)63 mmDrawn to scale. Every row is the same 140 mm cavity; insulation takes what air does not.Air enters from the soffit at the left. Under 25 mm is below code, and draws red.
The clear air path required over the insulation at the eave (Sources: NBC 2020 Article 9.19.1.3, adopted in Ontario; Natural Resources Canada, Keeping the Heat In)
Condition at the eaveClear air path above the insulationInsulation depth in a 140 mm cavityReading
Insulation blown tight to the deck0 mm140 mmblocked
Baffle at the wall junction25 mm115 mmNBC 9.19.1.3(2), the minimum
What NRCan recommends50 mm90 mm38 to 50 mm
Everywhere else above the insulation63 mm77 mmNBC 9.19.1.3(1)

How the Inch Gets Closed

Nobody sets out to block a soffit. It happens four ways.

  1. An attic top up with no baffles. A crew blows more loose fill across the attic, the hose reaches the eaves last, and the fill runs downhill into the overhang and packs against the sheathing.
  2. There never were any baffles. On an older house there may be nothing up there holding anything back at all.
  3. The soffit was painted. Gibraltar Building Products notes that perforated panels are easily painted shut with one or two coats, because the holes are small. From the ground the job looks freshly done.
  4. Solid panel went up where vented panel belonged. Solid soffit is the right product at porch ceilings and gable returns. From the driveway it looks much the same, so it also ends up on eaves.

Nothing about the first one is anyone's fault. The insulation is genuinely better afterwards. The house is genuinely warmer. The intake is genuinely gone, and none of those three facts contradicts the others. A rebate funded attic top up is one of the best things a homeowner can do to an Ontario house, and without baffles it is also one of the surest ways to bury a soffit.

The fix for the first two is not a roofing job. Baffles are an insulation trade item and they go in from inside the attic, not from a ladder outside. What we own is the outside half: the panel itself, its ventilation figure, the fascia it clips into, and the eavestrough hung off that.

Fitting a properly vented panel to a roofline whose intake is buried under a foot of cellulose achieves precisely nothing, which is why the attic is worth a look before anyone talks about colour.

Loose grey blown insulation covering an attic floor and running out towards the low edge where the roof deck meets the eave
Illustration: blown insulation running out toward the low edge of an attic. Whether the house still has intake is decided in the last two feet of that slope.

Not sure whether your soffit is doing anything?

We assess the soffit and fascia you have and tell you what it is doing for the attic. Free, and no obligation.

Book a Free Roofline Check

How Can You Tell If Your Soffit Is Breathing?

Three checks, in rising order of effort. Walk the perimeter and count how much of the run is perforated rather than solid. Look closely at whether those holes are open or sealed. Then, if you can reach the hatch safely, look down the rafter bays at the eave with a flashlight for daylight past the insulation.

The first check takes ten minutes from the driveway and settles more cases than people expect.

From the ground

  • Count the vented run. Note where the panel is perforated and where it is solid, elevation by elevation, then hold that against the drawing above.
  • Look at the holes, not the panel. Perforations sealed with paint, wasp nest or a decade of fine dust are exactly as useful as no perforations at all.

On plenty of houses the vented panel stops at the corners, or one whole elevation is solid because it was done in a different year by a different crew. That on its own can put a house under its intake target with nothing looking the least bit wrong.

From inside the attic

  • Find the hatch. The Building Code requires an access hatch to any attic space of 3 square metres or more that is at least 1 m long or wide and 600 mm high, so most houses have one somewhere.
  • Shine a light down each bay. You want a strip of daylight past the insulation in every rafter bay where it meets the eave.
  • Note which bays are dark. Daylight in some and not others is the signature of missing baffles rather than of a bad panel.

Two seasonal tells are worth adding. Frost on the nail points in February, a strip of ice along the overhang while the rest of the roof runs clear, or icicles returning to the same three spots every winter are all attic air problems that begin at the intake. Our summer roof maintenance checklist for Ontario covers the rest of that walkaround.

One thing that is not a soffit test, despite being sold as one: a ceiling stain. Water marks on an upstairs ceiling get blamed on ventilation constantly and are usually a real leak. Our guide to finding and repairing a roof leak covers how to tell the two apart, and the short version is that condensation stains are diffuse, seasonal and worst in late winter, while leaks are sharp edged and follow the rain. A dripping bathroom fan splits the same way, and our guide to a bathroom fan dripping water reads it by when the drip shows up.

What Is a Vented Fascia, and When Does a House Need One?

A vented fascia brings the attic's intake air in at the roof edge instead of under the overhang. Fascia vents go by several names, vented drip edge and edge vent among them, and they exist for houses with little or no soffit, where there is no panel to perforate. These products publish their airflow per lineal foot just as soffit panels do, and the best of them deliver more than twice what the common vented aluminum soffit does.

Plenty of Ontario houses have almost no overhang to work with: a rear addition, a modern box with the roof stopped at the wall line, a cottage with the rafters cut flush. Everything in the first half of this article assumes there is a soffit to breathe through. On those houses there is not, and the intake has to come in somewhere else.

The Code does not mind where. NBC 2020 Article 9.19.1.2 says required vents "may be roof type, eave type, gable-end type or any combination thereof", provided at least a quarter of them sit at the bottom of the space and they are spread evenly on opposite sides of the building. A vent at the roof edge is at the bottom of the space. It counts.

The products come in two families.

  • Through the fascia. Air comes up behind a slotted strip at the roof edge, through a gap left between the top of the fascia board and the roof deck. Lomanco's SV-10 is sold as a combination drip edge and continuous soffit vent, "perfect for homes built with little or no overhang", rated at 6.3 square inches a foot, and its instructions want that gap at least half an inch. DCI's FasciaVent lets air enter "through the fascia board, under the roof decking" at 9 square inches a foot.
  • Through the deck, under the shingles. A slot is cut in the roof sheathing a few inches up from the edge, and a low vent is shingled in over it. Air Vent's Edge Vent publishes 9 square inches a foot, DCI's SmartVent is rated at 8.9 in its ICC-ES evaluation report, and Owens Corning's VentSure InFlow publishes 10.

Run them against the same 1,500 square foot bungalow from earlier, which needs 360 square inches of intake, and the arithmetic turns over.

Feet of eave needed for the same 360 sq in of intake: roof edge vents against a common vented soffit panel (Sources: Owens Corning, Air Vent, DCI and its ICC-ES report ESR-2484, and Lomanco published net free area; Gentek Product Directory)
roofline this vent needsroofline the house does not have100 ft of eaveOwens Corning InFlow, deck slot10 sq in/ft64 ft to spare36 ftAir Vent Edge Vent, deck slot9 sq in/ft60 ft to spare40 ftDCI FasciaVent, in the fascia9 sq in/ft60 ft to spare40 ftDCI SmartVent, deck slot8.9 sq in/ft60 ft to spare40 ftLomanco SV-10 vented drip edge6.3 sq in/ft43 ft to spare57 ftGentek 16 in 2-panel soffit4.02 sq in/ft10 ft to spare90 ft04080120 ftEach run is 360 sq in of intake divided by the product's own figure.Each figure is the maker's own published net free area per lineal foot.
Feet of eave needed for the same 360 sq in of intake: roof edge vents against a common vented soffit panel (Sources: Owens Corning, Air Vent, DCI and its ICC-ES report ESR-2484, and Lomanco published net free area; Gentek Product Directory)
Soffit panelPublished ventilation per lineal footFeet of it needed for 360 square inches of intakeAgainst 100 feet of eave
Owens Corning InFlow, deck slot10 sq in36 ft64 ft to spare
Air Vent Edge Vent, deck slot9 sq in40 ft60 ft to spare
DCI FasciaVent, in the fascia9 sq in40 ft60 ft to spare
DCI SmartVent, deck slot8.9 sq in40 ft60 ft to spare
Lomanco SV-10 vented drip edge6.3 sq in57 ft43 ft to spare
Gentek 16 in 2-panel soffit4.02 sq in90 ft10 ft to spare

Where an Edge Vent Stops Working

Read that drawing next to the soffit one. The common 16 inch vented aluminum panel needs 90 feet of a 100 foot eave. Every roof edge vent on the list does the same job in 36 to 57 feet. A house with no overhang is not stuck. It needs a different product, chosen by its number like everything else here.

Four limits come with them, and most are printed by the makers themselves.

  1. The air still has to get past the insulation. An edge vent feeding an eave packed with cellulose does no more than a vented soffit would. The 25 mm baffle rule applies either way.
  2. Pitch. Edge Vent wants at least 3 in 12, SmartVent and InFlow 4 in 12. DCI pitches FasciaVent at roofs under 4 in 12, below where SmartVent and InFlow are rated.
  3. Mixing. Makers disagree. Owens Corning's sell sheet says not to use InFlow with soffit vents, yet also offers it as a supplement to existing under eave vents. Air Vent allows two intake types where both see similar wind and pressure. Follow the instructions of the product going on your roof.
  4. It is a roofing detail. A deck slot is cut under the bottom shingles, so a re roof is the natural time to add one.

US guidance shows what is at stake. The US Department of Energy's Building America Solution Center doubles the ratio to one square foot of vent for every 150 of ceiling when a house cannot have ventilation openings at the bottom of the roof at all. An edge vent is that bottom opening, which is what keeps a house with no overhang on the usual 1 in 300. Canada's Code doubles the ratio only for low slopes and roofs framed with joists.

Roof edge of an Ontario house with almost no overhang, where a slotted white vented drip edge runs above the fascia and eavestrough instead of a soffit
Illustration: a house with almost no overhang. The intake comes in at the roof edge itself, through a slotted vent above the fascia.

Now the Water Half: What the Fascia Is Holding Up

Fascia is the board that closes the ends of the rafters and gives the eavestrough something to hang from. It is the only part of the roof edge doing structural work, and on almost every Ontario house it is softwood, which rots once it gets wet and stays wet.

Everything at the roof edge is fixed to it. The eavestrough hangers screw through the trough and into the board. The drip edge tucks behind it or over it depending on the detail. The bottom course of shingles overhangs it. On some houses the soffit panel clips into a channel nailed to it as well, which means a soft fascia takes the soffit down with it.

The aluminum on the outside is a cover, and it is worth understanding what that cover is and is not. Fascia cover comes in flat stock bent on site or in preformed lengths: Gentek, for example, lists 4, 6, 8 and 10 inch faces in 9 foot 10 inch lengths, in economy, standard or heavy gauge depending on the face, ribbed or plain. It is a maintenance finish. It ends the repainting and it keeps rain off the face of the board. It adds no strength, it holds no fasteners, and it is perfectly capable of looking immaculate over a board that has turned to compost.

That last sentence is why the board, not the cover, is the thing to have checked before anyone quotes. A length of capping comes off in minutes, and the wood behind it tells you which of the four causes below has been at work.

Roof edge of an older house where aluminum fascia capping has been peeled back exposing a dark rotted wooden fascia board underneath
Illustration: aluminum capping peeled back from a fascia board that has rotted behind it. A clean cover says nothing about the wood.

Why Is My Fascia Rotting?

Almost never because of the fascia. Rotten fascia in Ontario has four upstream causes and every one of them is water arriving where it should not: a trough overflowing at the back, a missing or short drip edge, shingles that stop before the trough, and ice standing on the overhang every February.

Here they are.

1. The eavestrough overflows backwards

A blocked trough does not spill neatly over the front. Debris packs at the outlet, the water backs up, and the easiest way out is over the inside lip, straight down the back of the trough and onto the board. The fascia never dries, because it is shaded, tight against the trough, and sealed behind aluminum.

Our guide to eavestrough cleaning in Ontario covers how often that genuinely needs doing here rather than how often it gets sold. If the trough refills every October, whether a gutter guard would actually fix it is the sensible next question. If it is an open joint or a run with no fall left rather than debris, our guide to eavestrough repair and the six faults behind it covers which fix that needs.

2. There is no drip edge, or it stops short

Drip edge is the L shaped metal along the eave that carries water off the deck and into the trough, instead of letting it curl back under the shingles onto the board. Plenty of older Ontario houses have none at all, and the National Building Code does not require one on a shingled eave, so nothing in the Code makes one appear.

Where it is fitted but sits short of the back of the trough, every heavy rain lays a line of water along the top edge of the fascia. That is properly a flashing question, and our roof flashing guide follows the rest of it down the roof, joint by joint.

3. The shingles stop too short

The bottom course has to overhang far enough to throw water clear into the trough. NBC 2020 has the starter strip extend approximately 12 mm beyond the eaves. Too little overhang and surface tension walks the water back underneath, onto the drip edge and the board.

This turns up on re roofs done in a hurry, and on roofs near the end of their life where the bottom course has curled upward and lost its throw. A roof whose bottom course no longer lies flat is telling you about its remaining years as well as about your fascia.

4. Ice stands on the eave

An ice dam parks a block of ice directly on the overhang for weeks at a time, and meltwater sits behind it against the fascia and under the first course of shingles. That is a ventilation and heat loss problem in origin, which brings the first half of this article round to the second.

Three of the 42 soffit and fascia jobs in our portfolio began with an ice dam at the roof edge, all in March 2025. On Harvey Street in Orillia an ice dam let water seep into the soffit and fascia, and the troughs and downspouts failed under the weight of the ice. On River Street in Sutton it backed water up in the eavestrough and damaged the soffit. On Lake Drive in Jackson's Point it brought the original eavestroughs down to the ground. In Orillia the rest of the soffit and fascia was still sound, so it became a soffit and fascia repair rather than a replacement: the damaged soffit sections were fixed and the sound runs stayed. If the ice is on your roof edge now, our roof snow and ice dam removal service deals with it before it reaches the board.

Notice what is not on that list. Nothing about the grade of the wood, the paint, or the aluminum. Fascia is a downstream part. It records what the roof edge above it and the trough in front of it have been doing for ten years, which is exactly why replacing it without fixing them is money set on fire.

One more entry point deserves naming. The City of Toronto's own wildlife proofing guidance lists the soffit among the places animals get in: inspect it from a ladder all around the house, repair or replace any loose or rotten soffit, and cut down overhanging branches. A panel that has dropped because the board behind it went soft is exactly that loose soffit, and once the overhang is open the attic is open.

Open roof overhang on a stucco house on Harvey Street in Orillia with the ice damaged soffit taken down, exposing the rafter tails above three ladders
Harvey Street, Orillia, March 2025: the soffit an ice dam had soaked, taken down. The sound runs stayed and the damaged sections were repaired.

Capping Over Rot: What Aluminum on Bad Wood Buys You

Capping is the cheapest thing anyone can quote on a roofline, and on the right house it is the right answer. On the wrong house it is a postponement with a nice finish.

The test takes seconds and no tools worth mentioning. Push a screwdriver into the board at the outlet ends, at the low corners and anywhere the trough shows a stain. Sound spruce resists. Rotted spruce takes the shaft to the handle and comes back with wet fibre on it. Do it at every point where a downspout drops, because that is where the water has been.

What is behind the aluminumWhat it needsWhy
Sound and dry the whole runCap itThe cover ends the painting cycle and keeps rain off the face. Nothing else is needed
Soft in patches, sound betweenCut out and replace the bad lengths, then cap the runA board is cheap. Coming back is not
Soft the length of the runReplace the boardCapping it changes nothing except how long before you find out
Rafter tails soft as wellSister the tails first, then new boardThe tails are structure. Hangers pull out of soft ends and the trough sags again

A wet board capped in aluminum looks perfect on handover. The failure comes later, when the trough hangers pull out of soft wood and the run starts to sag, and by then nobody remembers who did the work. If you get two quotes and one is much cheaper, the question to ask is not about the aluminum. Ask whether the board is being replaced, and ask to be shown the wood.

Capping sound wood, on the other hand, is good value, and often the right call. A painted wood fascia needs repainting for as long as you own it, and on a fascia that is ladder work every time. Aluminum ends that.

Get the board looked at before you get it covered

Ask us to check the board under the cover before anything is quoted. 10 year workmanship warranty, $5 million liability insurance, and the final 10 percent due only once you are satisfied.

Get a Free Soffit and Fascia Quote

Aluminum, Vinyl or Wood?

Aluminum for almost every Ontario roofline. It holds its shape through freeze and thaw, it comes with a factory baked finish so there is nothing to repaint, and it can be brake formed on site to fit a roof edge that is nowhere near straight. Vinyl is cheaper and, in some profiles, ventilates considerably better. Wood is a look and a commitment.

The material argument at the roofline is not the same as the material argument on the walls. Our guide to choosing a siding material that lasts in Ontario works through cladding, where the trade offs are about appearance, fire and repainting. Up at the eave the questions are narrower: does it stay flat, does it vent, and can it be made to fit a house that settled forty years ago.

MaterialWhere it winsWhere it losesNotes for Ontario
AluminumDimensionally stable, brake formed to fit, factory finish, does not rotDents. A ladder butt or a hailstone leaves a mark that does not come outThe default here. Standard or heavy gauge is worth asking about
VinylCheapest, never dents, the best ventilating profiles beat aluminum outrightMoves a lot with temperature, so it wants correct expansion gaps at every channelFine on a soffit, which is shaded and unloaded. Weaker as fascia cover
WoodThe only right answer on a heritage detail, an exposed rafter tail, or a stained cedar entranceWants repainting for as long as you own it, on a ladderWe fit it where the house asks for it, and we tell you what it will cost you in upkeep

Two specifics that are worth having in your head when the quote arrives.

Aluminum soffit and fascia are both sold in more than one thickness. Gentek's directory lists its aluminum soffit in standard and heavy gauge, and its fascia cover in economy, standard or heavy depending on the face. The difference shows up the first time somebody leans a ladder against the fascia. Ask which gauge is on the quote.

Panels come in fixed lengths, and that changes the seam count on a long run. Gentek's 16 inch aluminum soffit runs about 12 feet 2 inches per panel, and its fascia cover comes in 9 foot 10 inch lengths. On a 50 foot elevation that is at least five joints in the fascia whatever anybody does, so ask how those joints will be lapped and which way they will face. Facing them away from the street costs nothing.

The one genuinely surprising line in that table is the vinyl one. The best ventilating vinyl profile in the Gentek directory delivers 10 square inches per lineal foot against 5.46 for the best aluminum in the same book. If a house is fighting for intake and the look allows it, that is a real answer rather than a compromise, and it costs less.

What Does Soffit and Fascia Replacement Cost in Ontario?

Most Sherak soffit and fascia installations run $1,500 to $4,000, depending on the material, the size of the house and how complicated the roofline is. What moves the number is not the aluminum. It is how much wood is behind it, and how much roofline there is to cover.

Price this by the length of the roofline, never by the floor area of the house. The 30 by 50 foot bungalow from earlier has 100 feet of eave as a gable and 160 as a hip: the same house, 60 more feet of soffit and fascia. Dormers, returns and bump outs add more, one hand formed piece at a time.

The quote is free, and it should name the panel, the gauge and what happens to the board. The next section is what moves the number between the two ends of that range.

What Actually Moves That Price

Here is where the difference between a $1,500 job and a $4,000 one goes.

  • Rotten board. Capping sound wood is one price. Cutting out and replacing lengths of 1x6 or 1x8 is another, and it is the largest single variable on the job.
  • Height and access. A bungalow is ladder work. A three storey rear elevation over a walkout is staging, and staging is time.
  • How cut up the roofline is. Every dormer, gable return, bay window and corner is a stop, a measurement and a hand formed piece.
  • Whether the eavestrough goes back up. It has to come off to do fascia properly, and an old sectional run with leaking seams is rarely worth refitting.
  • Rafter tails. Soft tails must be sistered before anything new is fixed to them. Never optional.

That fourth point is where homeowners most often decide to save and most often regret it. If the trough is coming down anyway and it is full of pinholes at the seams, the labour to put it back is spent on a run with a few winters left in it. Our comparison of seamless and sectional eavestrough works through where those joints actually fail and what the difference costs per foot.

Ask what the number includes: strip and disposal of the old material, new vented soffit and fascia cover, new board where the wood is gone, refitting the eavestrough on sound hangers, and the workmanship warranty. Then ask what it leaves out. Attic baffles and insulation, and any roof repair found above the fascia, belong in their own line, quoted plainly rather than folded in quietly.

If a roof is being priced at the same time, our full breakdown of roof replacement cost in Ontario sets out how the roofline items sit inside a larger job, and why doing them together almost always beats doing them apart.

The Three Jobs This Should Ride Along With

Soffit and fascia rarely justify a mobilisation of their own, and our own record says so more bluntly than any argument. Every soffit and fascia job in our published portfolio, 42 of them from 2021 to 2026, came with other work. 37 included eavestrough work, 26 included siding, and not one was soffit and fascia alone. The calendar below lays every one of them out by the month it was done.

Three jobs put a crew at exactly the same height with exactly the same access, and folding the roofline into any of them saves real money.

  1. A re roof. The eavestrough is coming off and the drip edge is being replaced anyway, so the new edge lands on new wood and the whole detail gets built once rather than assembled from two different decades. Three of the 42 came with a roof, among them the metal roof, siding, soffit, fascia and insulation on a Brechin bungalow in 2022.
  2. A re clad. New siding beside original aluminum soffit is the most visible mismatch on a house, because the two were never going to age the same way. In Bradford in 2026 the soffit, fascia and trim went on in black with the new siding over a brick ground floor.
  3. An eavestrough replacement. The trough has to come off to touch the fascia, and the fascia has to be sound to hold the trough.

On District Avenue in Vaughan in May 2025 the third one meant all of it at once: vented aluminum soffit, aluminum clad fascia, eavestrough, downspouts and pot lights, in three days.

On a re roof this is close to free money, because the tear off already pays for the access and the disposal bin is already on the driveway. If shingles are going on this year, ask for the roofline to be priced alongside them rather than after.

On a re clad, the colour argument decides it. A wall finished this year against soffit fitted decades ago reads as unfinished from the street even when both are white, because the old aluminum has chalked and the new panel has not. The same gap opens inside a single wall of vinyl, which our siding repair guide draws out panel against panel. Our siding service covers the walls, and the wider picture is in our complete guide to siding in Ontario.

On an eavestrough job the two are simply the same job seen from different ends, which is why 37 of those 42 jobs included the trough and why our seamless eavestrough service and the roofline get quoted together. If the run also needs guards, our leaf guard service goes on in the same trip rather than a second one.

The calendar also answers whether this can wait for spring. It does not have to: 10 of the 39 dated jobs were done between November and February, including new houses in Aurora in December 2024 and in South River on 2 January 2025. February is the one empty month, and March, when the ice lets go, is the busiest after October.

The exception is rot that has already reached the rafter tails, or an overhang an animal has opened. That is not a scheduling decision and it should not wait for a convenient season. Our roof repair and emergency service takes those on their own.

Every soffit and fascia job in Sherak's published portfolio, by month and by what else was on the job (Source: Sherak project records, 2021 to 2026)
With eavestrough and siding (21)With eavestrough (16)With siding (5)Soffit and fascia alone (0)Ice dam repair42 jobs. 37 included eavestrough work, 26 included siding,and 0 were soffit and fascia alone.Nov to Feb: 10 of 39 dated jobsJ2FM6A3M4J1J3A3S1O8N4D4n/d339 of the 42 jobs carry a month in the record; the rest standin the last column.Ringed: the 3 jobs that repaired damage from an ice dam.
Every soffit and fascia job in Sherak's published portfolio, by month and by what else was on the job (Source: Sherak project records, 2021 to 2026). 42 jobs: 37 with eavestrough work, 26 with siding, 0 soffit and fascia alone. Nov to Feb: 10 of 39 dated jobs.
JobMonthEavestrough workSidingNote
Bradford Siding, Soffit and Fascianot recordednoyes
Jackson's Point Siding, Soffit, Fascia and Eavestroughnot recordedyesyes
Kennedy Rd ProjectNovyesyes
McCaffrey Road ProjectMayyesno
Monash ProjectJanyesno
District Ave. Soffit, Fascia, Eavestrough, and Pot Light installation projectMayyesno
Lake Dr, Jackson's Point ProjectMaryesyesice dam
River St, Sutton ProjectMaryesnoice dam
Orillia Harvey St ProjectMaryesnoice dam
South River, Cedar Ct ProjectJanyesno
Georgina, Willow Beach ProjectDecyesyes
Aurora, Windham Trail ProjectDecyesno
Eagle Lake Road, South River ProjectNovyesno
Old Homestead ProjectOctyesyes
Side Road ProjectOctyesyes
Ritva Court ProjectOctyesno
Lagoon City ProjectOctyesyes
Adelaide ProjectOctnoyes
Woodbridge ProjectMaryesyes
Udora ProjectJulyesyes
Aberdeen ProjectMayyesno
Victoria Harbour ProjectSepyesyes
Georgina ProjectMaryesyes
Port McNicoll ProjectMayyesno
Pefferlaw ProjectDecyesyes
Oshawa ProjectMaryesno
Orillia ProjectAugyesyes
Newmarket ProjectApryesno
Kellena Dr ProjectApryesno
Innisfil ProjectOctnoyes
Keswick Siding ProjectAugyesyes
Pinary Ln ProjectNovnoyes
High Street ProjectDecyesyes
Lake dr ProjectOctyesyes
Downtown ProjectAugnoyes
Brechin ProjectOctyesyes
Angus ProjectJunyesyes
Oak Ridge ProjectApryesno
Aurora ProjectJulyesno
Peter Andrew Cres. ProjectNovyesyes
Georgian Bay, Siding, Soffit, Fascia, Eavestrough Installation Projectnot recordedyesyes
Magnolia Ave., Newmarket Project, Siding, Soffit, Fascia, Eavestrough installationJulyesyes

What to Ask Before You Sign

Six questions. The answers separate the quotes far better than the prices do, and every one of them is fair to ask on a driveway.

  • Which soffit panel, by product name, and what is its published ventilation figure per lineal foot?
  • How many feet of the run will be vented panel, and how many will be solid?
  • Is the fascia board being replaced or capped, and can you show me the wood?
  • Is a drip edge going in along the eave?
  • What happens to the eavestrough: new hangers or the old ones, same day or a separate trip?
  • What does the workmanship warranty cover, and for how long?

Vented on its own is not an answer to the first one. A contractor who does not know the figure has not thought about the intake. On a house with little or no overhang, the first question becomes which edge vent, and what its published figure is. On the second, check the answer against the arithmetic earlier in this article: corners and returns are legitimately solid, whole elevations are not. On the third, ask for a length of old capping to come off while you are standing there, and if the answer to the fourth is that the house never had a drip edge, that is a reason to fit one rather than a reason to skip it.

Ours runs 10 years on the workmanship itself. We carry $5 million in liability insurance, and 10 percent of the price is not due until you are satisfied with the job. Our guide to choosing a roofing contractor you can trust has the rest of the vetting checklist, including the paperwork worth asking for before anyone climbs a ladder on your property.

At Sherak we are based in Gormley and our crews work across York Region, Simcoe County, the Kawarthas and the GTA, from Newmarket and Aurora down through Richmond Hill and Vaughan into Toronto. We install and replace soffit and fascia on everything from a historic house on Main Street South in Newmarket to new builds in Aurora and South River, and from a pool house in Angus to homes along the south shore of Lake Simcoe.

Call 905 490 8800 or get a free quote and we will assess the roofline you have and give you a number for what is actually there.

Sherak Ltd, Head Office

12275 Woodbine Avenue, Gormley, ON L0H 1G0

Phone: +1 905 490 8800

Email: info@sherak.ca

New black aluminum soffit, fascia and eavestrough with a downspout and soffit pot lights on a brick house on District Avenue in Vaughan
District Avenue, Vaughan, May 2025: new vented aluminum soffit, aluminum clad fascia and eavestrough, with pot lights set in the soffit.

Frequently asked questions

What is the difference between soffit and fascia?
The soffit is the flat panel under the roof overhang, and its job is to let outside air into the attic through its perforations. The fascia is the vertical board across the ends of the rafters, and its job is to close the roof edge and carry the eavestrough. They sit inches apart, they are quoted together, and they fail for entirely different reasons.
How do I know if my soffit vents are blocked?
Walk the perimeter and count how much of the run is actually perforated rather than solid, then get close enough on a stepladder to see whether the holes are open or sealed with paint and dust. The definitive check is from inside the attic: shine a light down each rafter bay toward the eave and look for a strip of daylight past the insulation. Daylight in some bays and not others means baffles are missing.
What is a vented fascia?
A vented fascia, also sold as a fascia vent or a vented drip edge, lets the attic's intake air in at the roof edge on houses with little or no soffit. The products publish their airflow per lineal foot: DCI's FasciaVent is rated at 9 square inches a foot and Lomanco's SV-10 vented drip edge at 6.3, against 4.02 for Gentek's common 16 inch vented aluminum soffit. Like a soffit, it only works if the air can get past the insulation inside.
Can I replace the fascia and leave the soffit?
Sometimes, and it is a fair question when the budget is tight. The soffit panel usually clips into a channel fixed to the fascia, so the panel has to come down at least at the edge to do the board properly. If the existing soffit is a well ventilated panel in good condition, it can go back up. If it is solid panel, painted wood, or a low ventilation profile, replacing it while the run is already open costs a fraction of coming back for it.
How long does aluminum soffit and fascia last in Ontario?
No standard publishes a service life for aluminum soffit and fascia, and we would rather not invent one. The aluminum does not rot and carries a factory finish, so it does not need repainting. What ends the life of the assembly is almost always the fascia board underneath, an eavestrough that has been overflowing onto it, or a dent from a ladder or a falling branch. That is why the condition of the wood, not the metal, is the thing to ask about.
Will new soffit and fascia stop ice dams?
Not on their own. An ice dam is made by heat leaking into the attic and melting snow on the roof deck, and CMHC's fix is to seal the attic air leaks and insulate thoroughly. Restoring blocked intake helps the attic dry, and it is often the cheapest single thing available, but if the ceiling below is leaking warm air the dam will keep forming. Air sealing and insulation come first, and they belong to a different trade.
Do you have to take the eavestrough off to replace fascia?
Yes, on any job done properly. The eavestrough is screwed through into the fascia board, so the board cannot be replaced or even inspected with the trough hanging on it. The run comes down, the board and the capping are done, and the trough goes back up on sound hangers. If the trough is old, sectional or leaking at the seams, that is the moment to decide whether it goes back up at all.
Can soffit and fascia be replaced in winter?
Yes. Ten of the 39 dated soffit and fascia jobs in our portfolio were done between November and February, including a new house in Aurora between 20 and 28 December 2024 and another in South River on 2 January 2025. The exception is ice on the roof edge, which has to come off first.

Share this article

EA

Written by

Emad Alikhanpour

Roofing & Exterior Specialist

Emad has 15 years of hands-on experience across roofing and every exterior service Sherak offers, from shingle and metal roofs to siding, eavestroughs, soffit and fascia, and custom flashing.

15 years in the trade · Roofing and exterior services

View profile

Reader reviews

Loading reviews...

Leave a review

Your rating

Ready to start your project?

Request a free, no obligation quote today, or call us for emergency roof repair.

Call NowFree Quote