Maintenance & Seasonal

Bathroom Fan Dripping Water? What the Timing of the Drip Tells You (2026)

Emad AlikhanpourRoofing & Exterior Specialist•November 10, 2026• 14 min read
Bathroom Fan Dripping Water? What the Timing of the Drip Tells You (2026)
On this page

Key takeaways

  • A bathroom fan dripping water in winter is usually condensation: warm, wet exhaust cooling in a duct that runs through a cold attic, then running back down to the grille.
  • Ten minutes of a 25 L/s fan in a steamy bathroom moves about 260 g of water vapour. Cooled to an average January day in York Region, about 220 g of it cannot stay in the air.
  • Below freezing that water sticks to the duct as frost, which is why a fan can drip on a mild afternoon days after anyone showered.
  • A drip that comes with rain rather than showers is a leak at the roof vent or its flashing, which is a roof repair, not a duct problem.
  • The National Building Code wants bathroom exhaust outdoors, never into the attic, through a sealed duct insulated to at least RSI 0.5 and supported so it cannot sag.

A bathroom fan dripping water in an Ontario winter is usually the shower coming back. Ten minutes of a Code-minimum 25 L/s fan pulls about 260 g of water vapour out of a steamy bathroom, and if the duct is as cold as an average January day in York Region, about 220 g of it cannot stay in the air. It condenses, it freezes, and sooner or later it runs back down to the grille.

At Sherak, we replace failed bathroom exhaust vents on the roof and add new ones. The cap up there is a hole through the deck like any other, sealed into the shingles the same way our custom flashing seals a chimney or a wall. This guide reads the drip by when it happens. Minutes after a shower, days later on a thaw, and during rain are three different faults with three different fixes, and the timing tells you which one you have before anyone climbs a ladder.

Why Is My Bathroom Fan Dripping Water?

Because warm, wet air from the shower is cooling inside a duct that runs through a cold attic. Once that air drops below its dew point it leaves water on the duct wall, or frost below freezing, and gravity brings it back to the fan. Less often, the water is rain or meltwater getting in at the roof vent.

The fix depends on which, and the quickest way to tell is a calendar, not a ladder. Keep track of when the drip shows up for a week, then match it here:

When it dripsWhat is happeningWhere the fault is
Within minutes of a shower, on a cold dayCondensation running back down the ductThe duct: too long, too cold, sagging, or climbing to the roof with no way to drain
On a mild or sunny afternoon after a cold spell, with nobody showeringFrost that built up in the duct or the attic is meltingThe duct, or exhaust escaping into the attic
During rain, in any seasonWater getting in around the roof ventThe vent cap, its flashing, or the shingles around it
During a thaw, with snow on the roof and ice at the eavesMeltwater backing up under the shinglesAn ice dam, or snow melting around the vent
A little all winter, with a damp smell in the atticExhaust leaking into the attic and frosting the roof sheathingA loose or missing duct connection, or a fan never vented outside

The first two rows are one fault seen at two temperatures, and the next three sections take them in order. Water dripping from a bathroom fan only during rain is a different animal, a roof leak, and it has its own section further down.

Ten Minutes of Steam: How Much Water Goes Up the Duct?

About 260 g of water vapour for every ten minutes a 25 L/s fan runs while the bathroom is steamy. Cool that air to an average January day in York Region and about 220 g of it, roughly 85 percent, can no longer stay in the air. It has to land somewhere, and in winter it lands as frost.

The 25 L/s comes from the National Building Code of Canada 2020, the model on which Ontario's 2024 Building Code is based: Sentence 9.32.3.7.(4) asks for a bathroom exhaust fan rated at no less than that. The rest is physics anyone can check. Take a steamy bathroom at 22°C and 90 percent relative humidity: that air carries about 15 g of water in every kilogram of dry air. Its dew point is 20°C, so it starts shedding water on anything cooler than that, and above an Ontario ceiling in winter, everything is cooler than that.

The duct temperatures in the chart are the 1991 to 2020 climate normals for Toronto Buttonville Airport, an Environment Canada station in York Region: an average November day at 3.3°C, an average January day at minus 6°C, and a January night at minus 10.1°C.

Read each fill as a ceiling, not a forecast. It is what the air must give up if it cools all the way to the attic's temperature before it gets out, and a short, insulated duct gets much of it outside first. The attic also runs a little warmer than outdoors. In their attic ventilation guidelines, Wayne Tobiasson, James Buska and Alan Greatorex of the US Army's Cold Regions Research and Engineering Laboratory sized attic venting to hold an attic near minus 1°C when it is about minus 6°C outside. That barely moves the answer: at minus 1°C the air still has to shed about 200 g, three quarters of what it carries.

Two things in the chart matter more than the totals. November is the only row in blue: above freezing, the water runs back down the duct within minutes. From December on it freezes to the duct wall instead, and frost does not drip until the weather turns.

Water a steamy bathroom's exhaust must give up in a cold duct, per 10 minutes of a 25 L/s fan (Sources: NBC 2020 Sentence 9.32.3.7.(4); Environment and Climate Change Canada 1991 to 2020 Climate Normals, Toronto Buttonville Airport; Magnus formulas, Alduchov and Eskridge 1996)
Drops out as water, and drips nowFreezes to the duct as frost, and drips on the thawStill vapour, carried out of the roof capEach duct's full length is all 260 g of vapourthe exhaust carries. The filled part cannot stay in the air.One measuring cup, 250 mLNovember3.3°Caverage day180 gwater, 68%December−2.2°Caverage day205 gfrost, 79%January−6.0°Caverage day220 gfrost, 85%January−10.1°Caverage night low235 gfrost, 89%February−5.6°Caverage day220 gfrost, 84%March−0.2°Caverage day195 gfrost, 75%Room air: 22°C, 90% humidity, a steamy bathroom, pulledout at 25 L/s for 10 minutes. It condenses on anythingcolder than its 20°C dew point. Each fill is the most it mustshed if it cools to that temperature before it leaves.Magnus formulas (Alduchov and Eskridge, 1996).
Water a steamy bathroom's exhaust must give up in a cold duct, per 10 minutes of a 25 L/s fan (Sources: NBC 2020 Sentence 9.32.3.7.(4); Environment and Climate Change Canada 1991 to 2020 Climate Normals, Toronto Buttonville Airport; Magnus formulas, Alduchov and Eskridge 1996). Room air at 22°C and 90% relative humidity, 25 L/s for 10 minutes, carrying 260 g of water vapour, dew point 20°C.
Duct temperatureWhere the figure comes fromLands asGrams the air must give upShare of the vapour
November, 3.3°Caverage dayWater18068%
December, −2.2°Caverage dayFrost20579%
January, −6.0°Caverage dayFrost22085%
January, −10.1°Caverage night lowFrost23589%
February, −5.6°Caverage dayFrost22084%
March, −0.2°Caverage dayFrost19575%

Minutes After the Shower: Water Running Back to the Grille

When the duct is above freezing, the condensate forms as water and runs to the lowest point it can reach. If that low point is the fan, the drip arrives within minutes of the shower. Sags, long runs and a duct that climbs straight up to the roof all send it there.

Three things decide whether the water stays in the duct or comes back into the bathroom:

  • A sag. Flexible duct laid loose across the joists dips between them, and every dip is a trap that fills with water. The Code requires ducts to be permanently supported to prevent sagging (Sentence 9.32.3.11.(7)), and the US Department of Energy's weatherization job aid calls for flexible duct pulled tight, with no kinks, and supported at least every 4 feet.
  • Length. Every extra metre is more cold wall for the air to touch before it escapes. The same job aid asks for the shortest run possible, in a duct no smaller than the fan's outlet.
  • A climb to the roof. Any duct that rises from the ceiling to a roof cap drains backward by design, because whatever condenses on the way up runs down to the fan.

Canadian renovation writer Jon Eakes is blunt about that last one: it is not always possible to stop all the dripping from a duct in a Canadian attic, so drain the condensation outdoors rather than indoors. He would rather slope the duct down to an outlet in the end wall of the attic than go through the roof at all. Where it has to go through the roof, he points to roof exhaust hoods with a proper collar for the duct, built to drain most of the condensate out onto the roof.

Insulation helps, and the Code requires it. A duct that passes through an unheated space has to be insulated to at least RSI 0.5 (Sentence 9.32.3.11.(3)), about R-2.8. Eakes warns that the thin jacket on so-called insulated duct will not stop condensation in a cold attic on its own, which is why the slope and the length matter as much as the wrap.

Uninsulated foil bathroom exhaust duct sagging between attic trusses over pink insulation, frosted at its low point above a damp patch
Illustration: a sag between two trusses is a trap. Condensate pools at the low point, freezes there in January, and soaks the insulation below when it melts.

Days Later, on the Thaw: Frost Coming Back Down

Below freezing, the water from each shower freezes to the inside of the duct, or to the roof sheathing if exhaust is escaping into the attic. It builds up through a cold spell and melts all at once on the first mild or sunny day, so the drip arrives when nobody has used the shower for hours.

That is the frost half of the chart, and an Ontario winter gives it plenty of time to build. At Buttonville, an average January has 18 days that never climb above freezing, February about 15 and December about 12. A week of cold mornings and hot showers stacks frost in the duct and at the cap. Then the first day above zero sends it back at once, through the fan grille, around the fan housing, or as a fresh stain on the ceiling nearby.

Exhaust that ends up in the attic is the worst version, and the Code rules it out: exhaust ducts shall not discharge into heated or unheated enclosed spaces (Sentence 9.32.3.11.(2)). A duct that has slipped off the fan or the cap does exactly that. So does a fan that was never vented outside at all. The moisture frosts the underside of the roof deck and the nails, and it comes down as a slow drip or a damp ceiling on the next thaw. From outside it can show up as a melted circle out in the open field of the roof after the first snow, one of the patterns in our ice damming guide.

If there is ice along the eaves as well, the drip is more likely meltwater backing up under the shingles than anything the fan did. That calls for roof snow removal and ice dam removal, not duct work.

Black bathroom exhaust roof vent cap set into frosted grey shingles on a January morning, with frost feathers on the louvres and an icicle
Illustration: frost feathers on the louvres of a roof cap on a cold morning. The same thing happens inside the duct, out of sight, until the thaw.

When It Rains: A Leak at the Roof Vent, Not Condensation

A drip that turns up during rain, in any season, with no shower and no thaw behind it, is water getting in from outside. The usual causes are a cracked cap, flashing that has lifted, or shingles that no longer lap over the vent's base. That is a roof repair, not a duct problem.

A bathroom exhaust vent on the roof is a hole through the deck like a plumbing stack or a chimney, and it fails the same ways. The water rarely appears right under the hole, either. On a recent repair on a two-storey in Aurora, the stain sat over the dining room, but the source was a failed plumbing vent boot almost two metres away, a case our roof leak guide walks through. Rain that finds a bathroom duct on its way down can come out of the fan grille just as easily as out of a ceiling.

Water around a vent is small flashing work, and the published prices show why it pays to catch early. Resealing a sound flashing or replacing a cracked vent boot runs $150 to $600 in Ontario. A cracked boot is about $200 to replace before it leaks and about $1,200 once a winter of meltwater has soaked the ceiling and insulation below it. Our roof flashing guide shows how each penetration is sealed into the shingles, starting with the vents near the ridge.

Vents are worth counting on your own roof. The Stouffville roof we replaced in summer 2026 had a row of them, and each one was flashed into the new shingles on its own, as the Stouffville roof replacement photographs show. From the ground, a bathroom exhaust cap and an attic vent can look much alike, which is one more reason to trace the duct from the attic side before replacing anything.

Completed grey shingle roof in Stouffville seen from the ridge, with low profile vents and square roof vents set into the field
Stouffville, summer 2026: our finished tear-off from the ridge. Every vent on this roof is a hole through the deck, flashed into the new shingles one at a time.

Does the drip only come with the rain?

We will find where the water is getting in at the vent and quote the repair, free and with no obligation.

Get a Free Quote

What Does the Building Code Ask of a Bathroom Fan Duct?

Outdoors, sealed, insulated and supported. The National Building Code of Canada 2020 asks for a bathroom fan rated at 25 L/s or more that exhausts outside, never into the attic, through a duct insulated to RSI 0.5 or better in unheated space, with sealed joints, no sags, and the outlet 1,800 mm or more from a vented soffit.

RequirementWhat the Code saysWhere
Fan sizeA bathroom exhaust fan rated at not less than 25 L/s, where the house's principal ventilation fan does not draw from the bathroom9.32.3.7.(4)
How the fan is ratedAt 25 Pa of static pressure, the test point for this kind of fanTable 9.32.3.10.-A
Where it goesNot into a heated or unheated enclosed space, which rules out the attic9.32.3.11.(2)
InsulationAt least RSI 0.5, about R-2.8, where it passes through an unheated space9.32.3.11.(3)
SupportInstalled to avoid crushing and permanently supported against sagging9.32.3.11.(7)
JointsSealed with mastic, metal foil duct tape or the maker's specified sealant9.32.3.11.(8)
Outlet positionAt least 1,800 mm from air intakes and vented soffits9.32.3.13.(4)

Two lines in that table deserve a second look. The insulation figure is a floor, not a target: the Department of Energy job aid asks for R-8 on the same duct, nearly three times the Code minimum. And the fan rating is taken at a gentle 25 Pa of resistance, so a fan only moves its rated flow through a duct that is short and wide enough.

The Code says how short and how wide. Table 9.32.3.11.-A gives the longest duct each size can serve, and for a fan rated at 25 Pa moving 25 L/s it reads:

Duct diameterLongest run the Code table allows at 25 L/s
75 mm (3 in)None
100 mm (4 in)2 m
125 mm (5 in)6 m
150 mm (6 in)16 m

The Code's own note says the table gives very conservatively sized ducts, because it assumes a duct's equivalent length is four times its physical length. Flexible duct is sized more generously still: the Code takes it one diameter up, or treats it as twice its actual length (Sentence 9.32.3.11.(11)). Even so, the direction is the useful part. A long, narrow duct holds the fan below its rated flow, and slower air spends longer in the cold, which is the condensation problem all over again.

Ontario adopts this national text through its own amendment document, so for new ductwork your municipal building department has the final word.

Roof, Wall or Soffit: Where Should a Bathroom Fan Vent?

Through the roof or out a wall, never into the attic, and through the soffit only under strict conditions. A roof cap often gives the shortest run but makes the duct climb. An end wall lets the duct slope down and drain outside. A soffit outlet needs the soffit around it unvented or blocked, or the attic intake pulls the exhaust straight back in.

Good bathroom fan venting comes down to where the duct can end:

  • The roof. Usually the answer when the bathroom sits under the roof and the nearest outside wall is far away. Use a cap made for a bathroom fan, with a collar the duct fastens to and the backdraft damper the Code requires on a bathroom exhaust outlet (Sentence 9.32.3.13.(11)), and it has to be flashed into the shingles like any other bathroom fan roof vent.
  • An end wall of the attic. Eakes's preference where the attic reaches a gable: the duct can run downhill the whole way, so condensate drains outdoors instead of back to the fan.
  • The soffit. Here the Code allows an outlet only if the soffit is unvented, or blocked full depth for 1,800 mm on each side (Sentence 9.32.3.13.(5)).
  • Never the attic. Not into the insulation, not pointed at a roof vent, and not tucked into a soffit from the inside.

A wall outlet closer than 1,800 mm to a soffit has a version of the same rule: the soffit above it has to be unvented for a width of 1,000 mm to 3,600 mm, wider the closer the outlet sits (Table 9.32.3.13.-A). Both rules exist because a vented soffit is the attic's air intake, which our guide to soffit and fascia explains from the eave up. Exhaust blown out beside it gets drawn straight back into the attic, where it frosts the roof deck the same as a duct that was never connected. The bathroom exhaust vent on the roof is often the simplest way to avoid both problems, as long as the duct is short and the cap is flashed properly.

Replacing or Adding a Bathroom Exhaust Vent on the Roof

Start with the calendar. A week of noting when the fan drips tells you more than an afternoon on the roof: after showers points to the duct, after a cold spell points to frost, and during rain points to the vent and its flashing. If you cannot tell where your fan vents at all, a pre-winter roof inspection looks at the attic underneath as well as the shingles.

When the fault is on the roof, it is our work. We replace failed bathroom exhaust vents and add new ones, flashed into the shingles and backed by our 10 year workmanship warranty, with 10 percent of the price due only once you are satisfied. A leak that is already wetting a ceiling is a call for our roof repair crew. For anything else, get a free quote and we will trace the duct, check the cap, and tell you which of the three faults you have.

We are based in Gormley and work across York Region, Simcoe, Kawartha and the GTA, from Aurora to Barrie and Peterborough.

Sherak Ltd, Head Office

12275 Woodbine Avenue, Gormley, ON L0H 1G0

Phone: +1 905 490 8800

Email: info@sherak.ca

Fan dripping, or water at the vent?

We replace and add bathroom exhaust vents on Ontario roofs, flashed into the shingles. 10 year workmanship warranty and $5 million liability insurance.

Get a Free Quote

Frequently asked questions

Is it normal for a bathroom fan to drip a little in winter?
A drop or two on the coldest mornings can happen even on a decent installation, because some condensation is hard to avoid in a duct that runs through a Canadian attic. Drips after every shower, a puddle on the vanity, or a stain spreading around the grille are not normal. They point to a duct that is sagging, too long, poorly insulated or disconnected.
Should I stop using the bathroom fan in winter to stop the drip?
No. Switching it off leaves the shower's moisture in the house, where it ends up on cold windows and works its way into the attic through gaps in the ceiling. The National Building Code requires the fan that exhausts a bathroom to have a manual switch in that room, and it is there to be used. Fix the duct or the vent instead, and keep the fan running while the room is steamy.
Can a bathroom fan vent into the attic or the soffit?
Not into the attic. The National Building Code of Canada 2020 says exhaust ducts shall not discharge into heated or unheated enclosed spaces. A soffit outlet is allowed only when that soffit is unvented, or blocked full depth for 1,800 mm on each side, because otherwise the soffit vents pull the moist exhaust straight back into the attic. The attic's own vents are there to clear the vapour that leaks up through the ceiling, as our guide to roof ventilation explains, not a fan's worth of shower steam.
Will insulating the duct stop the drip?
It helps, and the Code requires at least RSI 0.5, about R-2.8, wherever the duct crosses an unheated space. Insulation alone often is not enough in a cold attic, though. Keep the duct short, support it so it cannot sag, seal every joint, and where possible slope it down to an outside wall so any condensate drains outdoors.
How can I tell a leaking roof vent from condensation?
Watch the timing. Condensation drips within minutes of a shower on a cold day, or on the first mild afternoon after a cold spell. A leak drips during rain, whether or not anyone has showered. If it only happens in the rain, the cap, its flashing or the shingles around it need attention, and that is roof repair work.

Share this article

EA

Written by

Emad Alikhanpour

Roofing & Exterior Specialist

Emad has 15 years of hands-on experience across roofing and every exterior service Sherak offers, from shingle and metal roofs to siding, eavestroughs, soffit and fascia, and custom flashing.

15 years in the trade · Roofing and exterior services

View profile

Reader reviews

Loading reviews...

Leave a review

Your rating

Ready to start your project?

Request a free, no obligation quote today, or call us for emergency roof repair.

Call NowFree Quote